1. Application |
| |
DZ47-100 is such features as delicate appearance, light weight, excellent and reliableperformance, high breaking capacity, rapid tripping and mounted by rail. Its enclosure and com-ponents adopts high fire-retarding and shock-resistance plastic of long durability. It mainly servesfor protecting the circuits of AC 50Hz, 230V of single pole, 400V of two poles or three or fourpoles from overload or short-circuit, and also for unfrequent making and breaking electricalapparatus and lighting circuit.It conforms with the standards of IEC60947-2.
|
| |
| |
2. Main Technical Parameter |
| |
| Type |
DZ47-100 |
| Pole |
1P |
2P,3P,4P |
| Rated current (A) |
63,80,100 |
| Rated voltage (V) |
230 |
400 |
| Ambient temperature |
-5oC~+ 40oC |
| Type of instantaneous release |
C,D |
| Rated short circuit breaking capacity Icn(kA) |
6 |
|
| |
| |
3. The over-current protection property
|
| |
| Ambient Temperature |
Initial Status |
Test Current |
Expected Result |
Expected Result |
NOte |
| 40±2oC |
Cold position |
1.05In(In≤63A) |
t≤1h |
Non-release |
- |
| Cold position |
1.05In (In[63A) |
t≤2h |
Non-release |
- |
| Carried out immedi-ately after previous test |
1.30In(In≤63A) |
t < 1h |
Release |
Current smoothlyrises to specified value within 5s |
| 1.30In (In>63A) |
t < 2h |
Release |
| -5~+40oC |
Cold position |
8.00In |
t≤0.2s |
Non-release |
- |
| Cold position |
12.00In |
t< 0.2s |
Non-release |
- |
|
| |
| |
4. Applicable conducting wire
|
| |
| Rated current(A) |
Nominal cross section of wire mm2 |
| 63A |
16 |
| 80A |
25 |
| 100A |
35 |
|
| |
| |
5. Dimension |
| |
|
|